EASTPOWER EA900 2KVA ( tower type ) 1800 watts

Minimum Order: 1

Available Stocks: 10

Weight: 12.00 kg/s

Dimension: 53.30 cm x 31.80 cm x 47.10 cm


₱ 27,930.00

No Reviews yet | Write a Review


Standard Delivery: No

Delivery Period: 3-5 days within Metro Manila and 5-7 days outside Metro Manila

(Note: Delivery period is dependent on Product Delivery)


Cash on Delivery not Available


EASTPOWER EA900 2KVA ( tower type ) 1800 watts 

FEATURES:

High frequency on-line double conversion technology


DSP (Digital signal processors) control technology


Active power factor correction (APFC), input power factor up to 0.99


Output power factor 0.9


Wide input voltage range (110V ~ 300Vac) and frequency range (40 ~ 70Hz)


Auto sensing frequency


50/60Hz frequency conversion


Cold start


Rear ventilation design and variable speed fan


Effective software and hardware protection


Quick and stable charging, 90% capacity restored in 3 h (standard model UPS)


Linear derating in low voltage input reducing battery discharging times


Settable delayed start when power is restored


Advanced battery management (ABM)


Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode, ECO mode and frequency conversion mode


Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)


Available Options


Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function, 12A charger (2-3KVA only) and built-in isolation transformer


MODEL

EA901PS

EA901PH

EA902PS

EA902PH

EA903PS

EA903PH

Capacity

1 KVA / 900 W

2 KVA / 1800 W

3 KVA / 2700 W

INPUT

Rated voltage

208 V / 220 V / 230 V / 240 Vac

Voltage range

110 ~ 176 Vac (linear derating between 50% and 100% load );
176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)

Frequency

40 ~ 70 Hz (auto-sense)

Power factor

≥ 0.99

Bypass voltage range

-25% ~ +15% (settable)

OUTPUT

Voltage

208 V / 220 V / 230 V / 240 Vac (settable via LCD)

Voltage regulation

± 1%

Frequency

45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)

Waveform

Sinusoidal

Crest factor

3:1

Harmonic distortion

≤ 2% (linear load); ≤ 5% (non-linear load)

Transfer time

Mains mode to battery mode: 0 ms
Inverter mode to bypass mode: 4 ms (typical)

Overload capability

105% ~ 125%: transfer to bypass in 1 min;
125% ~ 150%: transfer to bypass in 30 s;
> 150%: transfer to bypass in 300 ms

EFFICIENCY

Mains mode

≥ 90%

≥ 91%

≥ 92%

Battery mode

≥ 85%

≥ 86%

≥ 87%

ECO mode

≥ 95%

≥ 96%

≥ 97%

BATTERIES

DC voltage

24 V

36 V

36 V

48 V

72 V

72 V

72 V

96 V

96 V

Inbuilt battery

2×9 Ah

3×7 Ah

/

4×9 Ah

6×7 Ah

/

6×9 Ah

8×7 Ah

/

Charging current (max.)

1 A

6 A

1 A

6 A

1 A

6 A

Recharge time

8 h

ALARMS

Utility failure

4 s per beep

Low battery

1 s per beep

Overload

1 s twice beep

UPS fault

Long beep

COMMUNICATIONS

RS232 (standard) / USB (optional)

Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / Windows® 7 / 8 / 10

SNMP (optional)

Power management from SNMP manager and web browser

OTHERS

Operating temperature

0 ~ 40℃

Relative Humidity

0 ~ 90% (non-condensing)

Noise level

≤ 50 dB (1m)

Dimensions (W×D×H) (mm)

44×336×214

144×414×214

144×336×214

191×418×335

191×464×335

191×418×335

Packaged dimensions (W×D×H) (mm)

232×417×318

231×492×316

232×417×318

318×533×471

320×573×471

318×533×471

Net weight (kg)

9.5

13

6

18

25.7

10.5

27.2

32

11

Gross weight (kg)

10.5

14.2

7

19.5

27.4

12

29

34

12.5